Fisher DLC3010 Digital Level Controller
Fisher DLC3010 is an Emerson Fisher float type digital liquid level controller, paired with Fisher 249 series torsion tube float sensors, used in the petroleum, refining, and chemical industries to achieve three types of measurements: liquid level, oil-water interface, and liquid density. The current model DLC3010 has been discontinued, and we have a small inventory supply.
Important notice: The original DLC3010 has been discontinued, and our company can provide original inventory spare parts. We recommend upgrading to the new Fisher DLC3100
Working principle of Fisher DLC3010
| Item | Specification |
|---|---|
| Model | Fisher FIELDVUE DLC3010 |
| Measured Variable | Liquid Level, Interface, Liquid Density(SG) |
| Power Supply | 12~30V DC, 2-wire loop powered |
| Output Signal | 4-20mA DC (direct / reverse action), superimposed HART 7 |
| Saturation & Alarm | High saturation:20.5mA; Low saturation:3.8mA; High alarm:22.5mA; Low alarm:3.7mA |
| Accuracy | ±0.25% ~ ±0.5% Full Scale |
| Ambient Temperature | -40℃ ~ +80℃ |
| Process Temp (with 249 sensor) | Up to 425℃ |
| Display | Backlit LCD, shows mA, %, PV, temperature, fault code |
| Mounting | Matches Fisher 249 series caged / cageless displacer sensors(249B,249C,249P,249VS) |
| Communication | HART FSK 1200 baud |
| Certifications | ATEX, IECEx, FM, CSA, NEPSI |
Complete physical packaging certificates

Fisher DLC3010 Transmitter Key Features
✅ 3-in-1 Measurement: Liquid Level / Interface Level / Specific Gravity (Density)
✅ 2-wire loop power, 4–20mA analog output + HART® digital communication (1200 baud FSK)
✅ High accuracy: ±0.25% ~ ±0.5% FS, stable torque tube non-contact inductive sensing
✅ Built-in backlit LCD local display: show PV, percentage, mA value, temperature & diagnostic codes
✅ RTD temperature input for automatic specific gravity compensation
✅ Hazardous area certifications: ATEX, IECEx, FM, CSA for explosive environment
✅ Adjustable damping filter to suppress liquid turbulence ripple
✅ Compatible with 475 / 375 HART field communicator for onsite configuration, calibration & diagnostics
✅ NAMUR NE43 compliant alarm output
FAQ
A: DLC3010 is a digital displacer level controller for measuring liquid level, oil-water interface and liquid density in refinery & oil & gas process.
A: DLC3010 has been discontinued by Emerson. We provide original surplus stock, service parts and DLC3100 upgrade solution.
A: It is designed for Fisher 249 series displacer sensors (caged and cageless types).
A: 4-20mA analog + HART digital communication.
Introduction of Xi ‘an Lilu Trading Co., LTD
Xi ‘an Lilu Trading Co., Ltd. is a professional import and export focus on transmitter, flow meter, positioner instrument industry provider. We have a huge advantage in the following brand ROSEMOUNT, YOKOGAWA, HONEYWELL, SMC, IMI NORGREN, ABB, ENDRESS + HAUSER, FISHER, YTC, AZBIL, SIEMENS, SCHNEIDER and some European brands.
We look forward to your inquiry and hope that we can start the best cooperation.
Phone: +86-18392971088
البريد الإلكتروني: inquiry@lilutrading.com















المراجعات
لا توجد مراجعات بعد.